Obvius A8923-4 Installation Instructions
IO Module: Analog 4-20mA/0-10V and Pulse to Modbus
WARNING--REFER INSTALLATION AND SERVICING TO QUALIFIED PERSONNEL ONLY!
Read instructions throughly prior to install
This product is not intended for life or safety applications
Applications shown are suggested means of installing this product, but it is the responsibility of the installer to ensure that the
installation is in compliance with all national and local codes. Installation should be attempted only by individuals familiar with
proper installation techniques and with codes, standards, and proper safety procedures for control installations.
Installation, Wiring and Setup
1. Snap unit to existing DIN rail.
2. Connect power supply, network wiring, and sensor inputs as
indicated in wiring diagram.
3. Select network address as indicated by the diagram. Each
modbus device must have a unique address.
4. Auto-detect analog inputs: Make sure all analog devices are
properly installed and powered. Press the “LEARN” button.
Inputs will automatically be identified as 4-20mA or 0-10v.
5. Verify pulse inputs: Contact closure on pulse inputs will cause
red pulse LEDs to blink. Verify each pulse input is functioning
properly.
Modbus Point Map
Address Function Range Address Function Range
40001 Analog 1 Instantaneous reading. 0-4095 40017 Pulse State Register *See Note.
40002 Analog 2 Instantaneous reading. 0-4095 40018 Pulse 1 ontime LSW (seconds)
40003 Analog 3 Instantaneous reading. 0-4095 40019 Pulse 1 ontime MSW (seconds)
40004 Analog 4 Instantaneous reading. 0-4095 40020 Pulse 2 ontime LSW (seconds)
40005 Pulse 1 LSW 40021 Pulse 2 ontime MSW (seconds)
40006 Pulse 1 MSW 40022 Pulse 3 ontime LSW (seconds)
40007 Pulse 2 LSW 40023 Pulse 3 ontime MSW (seconds)
40008 Pulse 2 MSW 40024 Pulse 4 ontime LSW (seconds)
40009 Pulse 3 LSW 40025 Pulse 4 ontime MSW (seconds)
40010 Pulse 3 MSW 40026 Analog 1 min 0-4095
40011 Pulse 4 LSW 40027 Analog 1 average 0-4095
40012 Pulse 4 MSW 40028 Analog 1 max 0-4095
40013 Status Register *See Note. 40029 Analog 2 min 0-4095
40014 Firmware Version (111 = 1.11) 40030 Analog 2 average 0-4095
40015 Uptime Seconds LSW (seconds) 40031 Analog 2 max 0-4095
40016 Uptime Seconds MSW (seconds) 40032 Analog 3 min 0-4095
40033 Analog 3 average 0-4095
40034 Analog 3 max 0-4095
40035 Analog 4 min 0-4095
40036 Analog 4 average 0-4095
40037 Analog 4 max 0-4095
Seitenansicht 0
1 2

Inhaltsverzeichnis

Seite 1 - Modbus Point Map

Obvius A8923-4 Installation InstructionsIO Module: Analog 4-20mA/0-10V and Pulse to Modbus WARNING--REFER INSTALLATION AND SERVICING TO QUALIFIED PE

Seite 2 - Specification

Supported Modbus commands:0x03 Read Holding Registors0x06 Preset Single Register0x11 Report Slave IDAll other Modbus commands return "Illegal Fun